我有一個問題要為我的工作室保留AC連接。車間位於與車庫相連的房屋的另一側,達到95度。錢幣!我目前正在考慮購買DIY MINI SPLIT 12000 BTU 120v (Link to product here),我需要弄清楚如何正確地接線。

我很確定此插座與車間中的其他插座在電路上,因此如果我要知道這是一個問題。我的斷路器似乎已裝滿,因此可能無法佈線。

所以我的問題是,是否可以將外部插座轉換為必要的接線,以連接上述交流電源?

enter image description here

enter image description here

enter image description here

0

For the 12000 btu unit you linked to it is 120v. Are there any other loads on this outlet or circuit? A 12000 btu unit normally draws under 15 amps with an inverter. The one main concern I know about on these units are using a sealant like nylog blue to make sure the fittings do not leak. We had a class over a year ago they mentioned servicing these units the number 1 problem was leaking fittings. I have not used one but would use nylog blue . No interest in the company I use the product. As far as tapping that receptacle if nothing else is on that line I would feed a disconnect from the receptacle and use it that way.

As with all splits make sure to hang the unit level or slightly lower on the drain side. Do not kink the drain and cut the line off just above the ground.


0

As is often the case, "it depends". Code requires one outlet on the front of the house and one on the back as a minimum. I also believe outdoor outlets need to be on their own circuit these days. soooo, probably not code legal to do so. Also, since it's a permanently attached appliance, if it's current draw is over 50% of the amperage of the circuit, it can't share with outlets.